VARIOTEC 8 |
   |
VARIOTEC 8 Detecting Water Leaks using Hydrogen Tracer
Gas |
Click on any image to
enlarge
 |
The tracer gas, a mixture of hydrogen and nitrogen, is introduced
into the pipe with the suspected leak. The gas, being the lightest in the
atmosphere and made up of of small molecules, will exit at the leak and
make its way to the surface where it is detected by the highly sensitive
Variotec® 8 gas detector. |
VARIOTEC
8 FEATURES |
|
VARIOTEC 8 IN USE |
 |
- The surface over the route of the pipe is searched for traces of gas
using one of a selection of probes
- The VT8 detects gas down down to the lowest levels of parts per million,
allowing you to pinpoint the smallest traces of gas and also up to the
highest concentrations of volume percent levels (10,000ppm = 1 vol%)
which ensures that you can hone right into the area of interest without
reading overscale
- The large LCD display instantly responds to any changes in gas levels
|

|
- The escaping gas concentration is displayed both numerically and by
a quasi analogue scale making it very clear where the highest readings
are obtained
- The sensor used (there are two to allow more precise readings)and
the measuring scale automatically switches between the most suitable
range but can also be scaled manually to hone down the area of search
|
|
Why hydrogen? |

|
Hydrogen, at 5% in a balance of nitrogen,
is:
- non flammable
- non toxic
- non corrosive
- totally safe
- commonly used as a blanket gas in welding so is cheaply and readily
available from all the standard gas suppliers
- has the smallest and lightest molecules so permeates all surfaces
including concrete, tarmac, block paving and grass, rising quickly to
the surface
- rapidly disperses in air allowing you to hone in quickly to the source
- unlike helium, which has also been used for some types of leak detection
tracing, hydrogen is renewable and cheap;helium is finite and expensive
|
|
Variotec 8 locating probes |

|
- Carpet probes for long stretches of smooth surfaces
- Bell probes which concentrate the gas for localising in undergrowth
or on smooth surfaces such as kitchen floors
- Hand probes both telescopic and flexivle to reach into awkward areas
- Cone probes for localisation in bar holes you make in the ground
|
|
Charging and carrying |

|
- Parts and accessories are stored neatly in the hard protective carrying
case
- The VT8 may be charged directly from a 12 V cigar lighter socket in
a vehicle or from the mains
- The detector can be charged whilst remaining in the case
|
|
Variotec 8 Specifications |
|
| Sample intake:
|
Via built-in
membrane pump |
| Operating
time: |
≈ 8 hours
(with pump) |
| Power supply:
|
NiCd. Rechargeable
|
| Weight: |
1.5 Kg |
| Dimensions
(WxHxD): |
129x192x65
mm |
| Operating
temperature: |
-10 °C ...
+40 °C |
| Storage temperature:
|
-25 °C ...
+70 °C |
| Protected
to: |
IP 54 |
| Calibration:
|
Tracer gas
|
|